Clean and Regasket a Plate Heat Exchanger

How to clean a gasketed plate heat exchanger in place or with the pack open, and how to regasket it: glued or clip-on gaskets, groove preparation.

5 min read, with a 3D videoRead the article

Play the videoWatch on YouTube

Most plate heat exchangers lose performance slowly. The plates foul, the pressure drop rises, the outlet temperature drifts, and by the time someone opens the pack the gaskets have aged as well. Cleaning and regasketing are two separate jobs, but they are often done in the same shutdown. This is part 2 of our series on the gasketed plate heat exchanger; part 1 covers how to read gasket failure.

First decide: clean in place, or open the pack

Cleaning in place (CIP) circulates a cleaning liquid through the exchanger without opening it. It is quick and suits light fouling and regular cleaning. Opening the pack is needed when the fouling is heavy, when CIP no longer brings back the pressure drop and temperatures, or when you also want to inspect the plates and gaskets. A rising pressure drop at the same flow is the usual signal that cleaning is due.

Cleaning in place

  • Match the chemical to the fouling. Scale and mineral deposits respond to a mild acid; fats, oils, proteins and biological films respond to an alkaline cleaner.
  • Check the chemical against both the plate material and the gasket compound, and keep to the concentration and temperature limits given by the chemical supplier and in the manual for your model. A cleaner that is too strong or too hot is a common cause of swollen or hardened gaskets.
  • Chlorides attack stainless steel plates. Do not use hydrochloric acid or chloride-bearing cleaners on stainless plates, and rinse with water that is low in chlorides.
  • Circulate the liquid in the direction opposite to normal flow, and at a flow rate at least equal to the working flow, so that loose deposits are carried out.
  • Rinse with clean water until the outlet runs clear and neutral, then bring the unit back on line slowly.

Cleaning with the pack open

Before you loosen anything, draw a diagonal line across the side of the pack and number the plates, so every plate goes back in its place and the right way round. Loosen the bolts evenly, slide the plates apart, and clean each plate on both faces.

  • Hot water is preferred for jet cleaning. High-pressure water or steam is used on many models, with the lance held at about 45 degrees to the plate. Follow the manual for your model for the permitted pressure.
  • Use a soft brush and the right chemical for stubborn deposits. Never use a wire brush, scraper or sharp tool: a scratch on a plate starts corrosion and cracking.
  • Keep the jet away from the gasket and its groove at close range, so it does not lift the gasket.
  • Rinse and dry the plates before the pack is closed.

When to regasket

Opening the pack is the right moment to regasket if the gaskets show the signs described in part 1: hard, flat and glazed; swollen or sticky; weeping at the edge; or out of the groove. Once a pack has been opened, we advise fitting new gaskets rather than refitting the old ones, because old gaskets that have taken a set will not reseal reliably. Regasket the whole pack, not single plates: new gaskets beside old ones compress differently, and the pack will not close evenly.

Regasketing step by step

  1. Choose the compound against the media, the temperature and the cleaning chemicals, not just against what was fitted before. If the old gaskets swelled, the same compound will do it again. EPDM, nitrile and Viton each suit different duties.
  2. Remove the old gaskets. Glued gaskets peel off; on clip-on (glue-free) gaskets, release each clip.
  3. Clean the groove completely. On a glued plate, remove every trace of the old glue and any residue, and let the groove dry.
  4. Inspect the bare, clean plate before any new gasket goes on. Backlighting in a dark room is a quick check: a crack or pinhole shows as light coming through the plate. Finer cracks need a dye penetrant test. A plate that fails the check is replaced now, not after the pack is closed.
  5. Fit the new gasket. For a glued gasket, apply the glue specified for the gasket compound as a thin, even film, seat the gasket fully in the groove, and let the glue cure before the plates are stacked and the pack closed. For a clip-on gasket, check that every clip is seated.
  6. Look along each gasket for a section sitting on the edge of the groove instead of in it. That section will leak or be pinched when the pack is tightened.

Closing the pack is the last step and has its own rules: plate order, parallel frame plates, diagonal tightening and the tightening dimension on the nameplate. We cover it in a later part of this series. Until then, follow the tightening dimension on your nameplate and never go below the minimum.

Keep it from coming back

  • Note the pressure drop and the outlet temperatures when the unit is clean. A rise from that baseline tells you when the next cleaning is due.
  • Record the date, the cleaning chemical and the gasket compound used, so the next regasket is planned rather than forced.
  • Store spare gaskets cool, dry and in the dark, away from electric motors and welding, which give off ozone that ages rubber.

We supply replacement gaskets and plates for most major makes and can advise on the compound for your duty. Find your model in the plates and gaskets catalogue, or go straight to Alfa Laval, APV, Kelvion, Danfoss or API Schmidt-Bretten. Send us the plate model, the media and the temperatures, and we will advise on the compound and the next step.